Archive for December, 2009

Real time power metering early results

Tuesday, December 22nd, 2009

Now that the electrical metering is in place, we have some early graphs of power use over time: [gallery]


CUIT calculates preliminary PUE

Wednesday, December 16th, 2009

PUE = Total Facility Load / IT Load IT Load = 250kW (pp1,2,3,4,5,6,16) + 40kW (pp26,27) = 290kW Total Facility Load (winter w/o chw) = 290kW (IT) + 50kW (ATS2) + 85kW (ATS3 lieberts w/o chw) = 425kW Total Facility Load (w/chw) = 290kW (IT) + ??kW (ATS2) + 50kW (ATS3 lieberts w/chw) ...


NSF Workshop on HPCC Sustainability

Monday, December 7th, 2009

Columbia project team members will be participating in the NSF-sponsored workshop on High Performance Computing Center Sustainability May 3-5 at Cornell Univeristy.


IBM/Syracuse Green Data Center

Monday, December 7th, 2009

The IBM/Syracuse University Green Data Center was the subject of a full page ad in last weeks' NY Times.