Tuesday, December 22nd, 2009
Now that the electrical metering is in place, we have some early graphs of power use over time:
[gallery]
Posted in Uncategorized | No Comments »
Wednesday, December 16th, 2009
PUE = Total Facility Load / IT Load
IT Load = 250kW (pp1,2,3,4,5,6,16) + 40kW (pp26,27) = 290kW
Total Facility Load (winter w/o chw) = 290kW (IT) + 50kW (ATS2) + 85kW (ATS3 lieberts w/o chw) = 425kW
Total Facility Load (w/chw) = 290kW (IT) + ??kW (ATS2) + 50kW (ATS3 lieberts w/chw) ...
Posted in Uncategorized | No Comments »